BIDHISS III™ Three-Phase Power Conditioner Specifications

 

Model

Power Rating

Voltage 60 Hz

Load Capacity Amps

   1 KHz    Imped

Load Regulation +/-  %

Efficiency

BTU/hr Output

Case Code*

Dimensions

W x L x H (in.)

Weight (lbs)

TSD31005 5KVA 208-208/120 14 <0.8 hms 0.9% 97.5% <450 2 16.5" x 30" x 24" 300
TSD31010 10KVA 208-208/120 28 <1.4 hms 1.3% 97.5% <900 2 16.5" x 30" x 24" 350
TSD31015 15KVA 208-208/120 42 <0.8 hms 1.0% 98.0% <1100 2 16.5" x 30" x 24" 400
TSD31020 20KVA 208-208/120 55 <0.8 hms 1.2% 98.0% <1400 2 16.5" x 30" x 24" 450
TSD31030 30KVA 480-208/120 83 <0.8 hms 1.8% 98.2% <1900 3 18.5" x 30" x 33" 550
TSD31045 45KVA 480-208/120 125 <0.4 hms 1.3% 98.5% <2300 3 18.5" x 30" x 33" 750
TSD31054 54KVA 208-208/120 150 <0.8 hms 0.9% 98.6% <2700 3 18.5" x 30" x 33" 850
TSD31054 54KVA 480-208/120 150 <0.2 hms 0.9% 98.6% <2700 3 18.5" x 30" x 33" 850
TSD31054 54KVA 480-208/120 65 <0.2 hms 0.9% 98.6% <2700 3 18.5" x 30" x 33" 850
TSD31075 75KVA 480-208/120 208 <1.0 hms 0.9% 98.7% <3400 4 22" x 41" x 33" 1200
TSD31075 75KVA 480-208/120 90 <1.0 hms 0.9% 98.7% <3400 4 22" x 41" x 33" 1200
TSD31100 100KVA 480-208/120 278 <0.2 hms 0.9% 98.7% <4000 5 25" x 32" x 50" 1400
TSD31100 100KVA 480-208/120 120 <1.0 hms 0.9% 98.8% <4000 5 25" x 32" x 50" 1400
TSD31125 125KVA 480-208/120 361 <0.2 hms 0.9% 98.8% <5000 5 25" x 32" x 50" 1600
TSD31125 125KVA 480-208/120 150 <1.0 hms 0.9% 98.8% <5000 5 25" x 32" x 50" 1600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Back

BIDHISS I™ & BIDHISS II™

Model

Power Rating

Voltage

Load Capacity Amps

   1 KHz    Imped

Load Regulation +/-  %

Efficiency

BTU/hr Output

Case Code*

Dimensions

W x L x H (in.)

Weight

(lbs)

TSD1120 2 KVA 208-240/120 16 <1.9 hms 2.0% 96% <200 C 8" x 15" x 8" 56
TSD1128 2.8 KVA 208-240/120 24 <1.5 hms 2.0% 97% <250 C 8" x 15" x 8" 78
TSD2320 2 KVA 208-240/120 8 <1.7 hms 1.17% 97.3% <205 C 8" x 15" x 8" 62
TSD2330 3 KVA 208-240/120 12.5 <1.5 hms 1.23% 97.5% <260 C 8" x 15" x 8" 72
TSD2348 4.8 KVA 208-240/120 19.2 <.55 hms .70% 98% <335 D 8" x 21" x 8" 120
TSD2360 6 KVA 208-240/120 25 <2.4 hms .90% 98% <400 2 16.5" x 30" x 24" 222
TSD23100 10 KVA 208-240/120 41.7 <2.0 hms .90% 98.3% <560 2 16.5" x 30" x 24" 266
TSD23150 15 KVA 208-240/120 62.5 <.97 hms 1.10% 98.6% <715 2 16.5" x 30" x 24" 384
BIDHISS III™ Three-Phase Power Conditioner Specifications
Other combinations of input and output voltages, 50/60Hz, and three phase units available.
Specify input and output voltage when ordering. Specifications subject to change without notice 8/96
  • Impulse and Spike Protection--   All systems will withstand and protect against worst-case powerline disturbances, as defined by ANSI/IEEE C62.41-1980 category A and B ringwave and impulse, up to 6000V. With an input of 5000V category A ringwave, let-through of high frequency noise will be <10V NM and 0.5V CM, regardless of phase angle

    • Reliability-- All units built to UL 1012 standard.

    • Warranty--All units include a standard 5-year warranty.

    • *Case Codes - Rackmount available